Fluke i400E AC Current Clamp

  • Fluke i400E AC Current Clamp

主要特性

  • Compatible with most Fluke multimeters or mV ac measurement tools with these features:
    • 400 mV ac range
    • 19.05 mm banana jack inputs
    • Input accuracy of 2 % or greater to take full advantage of the accuracy of the product
    • Input impedance of >1 M?
  • 1 mV/A ac output guarantees easy current readings on you meter
  • CAT III 600 V safety rating
  • Specially designed to offer maximum utility in a very compact shape
  • Take accurate current readings
询价及预约演示

产品概述

The Fluke i400E AC Current Clamp is an ideal tool to extend current measurement. It is designed to work with the new Fluke 101, 106 and 107 palm sized digital multimeters, as well as most Fluke multimeters or other voltage measurement tools that accepts 19.05 mm shrouded banana plugs and has mV ac measurement functionality.

产品规格

Electrical specifications
AC current range

1 A to 400 A

Output signal 1 mV/A ac
Accuracy 2.0 % ± 5 digits (45 Hz to 65 Hz)
2.5 % ± 5 digits (65 Hz to 400 Hz)
Typical bandwith 5 Hz to 20 kHz
Working voltage 600 V ac rms, in compliance with IEC 61010-1 and IEC 61010-2-030
Load impedance 1 A to 400 A
Maximum non-destructive current 600 A
Jaw inner diameter 30 mm
Maximum wire size 600 MCM
Standard plugs 19.04 mm dual banana plugs
 
Safety specifications
Category rating IEC 61010-1 and IEC 61010-2-030/IEC 61010-2-031 and
IEC 61010-2-032: 600 V CAT III
Pollution Degree 2
Electromagnetic environment IEC 61326-1: Portable
 
General Specifications
Output cable length 1 m
Operating temperature -10 °C to +50 °C
Storage temperature - 30 ºC to +60 ºC
Relative humidity ≤90 % at 10 °C to 530 °C;
≤75 % at 30 °C to 540 °C;
≤45 % at 40 °C to 50 °C
IP rating IEC 60529: IP30 when jaw closed
Temperature coefficients Add 0.1 x specified accuracy for each °C above 28°C or below 18 °C.
Operating altitude 2,000 meters
Storage altitude 12,000 meters
Vibration requirements MIL-PRF-28800F, Class 2
Drop test requirements -10 °C, 1m, 6 sides, oak wood
Jaw impact test requirements Follow EN/IEC 61010-2-032:2012
EMI, RFI, EMC IEC/EN 61326-1
Dimensions (hxwxd) 146 mm x 62 mm x 34 mm
Weight 150 g